Compact capacity range
The small cylinder covers local AHU and duct humidity loads without an oversized steam package.
This single-cylinder electrode humidifier modulates from approximately 1.8 to 9 kg/h and has a documented maximum input of 7.6 kW. Supply options span 208-600 V, allowing the cabinet to match common facility electrical systems. Steam production depends on water conductivity because the cylinder water completes the electrical circuit, so inlet-water quality and automatic drain behavior are central to reliable operation.
The small cylinder covers local AHU and duct humidity loads without an oversized steam package.
Steam output follows water level and conductivity under the controller's fill and drain sequence.
Available electrical arrangements support 208-600 V facility supplies.
| Steam Output | 1.8-9 kg/h |
|---|---|
| Maximum Input | 7.6 kW |
| Steam Cylinders | 1 |
| Supply Voltage | 208-600 V by selection |
| Heating Principle | Electrode boiling |
| Feed Water | Conductive potable water within selected limits |
| Control | Modulating output |
| Drain | Automatic conductivity and scale management |
| Primary Duty | Small duct humidification |
| Customisation | Disponible en fonction de l'application prévue et de l'environnement d'exploitation. |
For small cleanroom AHUs, laboratories and local supply ducts requiring isothermal humidification from normal potable water.
Confirm steam load, voltage, water conductivity, cylinder type, control signal, distributor, hose length, drain cooling and BMS alarms.
Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.