Mid-capacity plant fit
The machine fills the capacity gap between a medium building chiller and the largest campus-scale selection.
The 1407 kW selection lengthens the heat-exchanger package to 5053 mm and raises evaporator flow to 60.49 l/s. Its published 200.5 kW input suits larger pharmaceutical and electronics plants that have moved beyond the smallest centrifugal frame but do not require the 2110 kW machine.
The machine fills the capacity gap between a medium building chiller and the largest campus-scale selection.
The extended frame accommodates the evaporator and condenser area required for the higher water flow.
A 200.5 kW input point supports electrical and energy planning at the stated cooling condition.
| Cooling Capacity | 1407 kW |
|---|---|
| Input Power | 200.5 kW |
| Evaporator Flow | 60.49 l/s |
| Dimensions | 5053 x 2469 x 2852 mm |
| Compressor Type | Centrifugal |
| Evaporator | Shell-and-tube water circuit |
| Condenser | Water-cooled shell-and-tube circuit |
| Capacity Control | Modulating chiller control |
| Installation | Indoor central plant-room base |
| Customization (Özelleşme) | Water-box connections, electrical supply and control interface can be configured for the intended application and operating environment. |
Larger pharmaceutical plants, electronics manufacturing, hospital campuses and clean production facilities with central cooling towers.
Water-box orientation, pressure rating, electrical starter, isolation, heat recovery, flow instrumentation and plant-control communication are available.
Bize boyutlarınızı, montaj koşullarınızı, performans hedeflerinizi ve gerekli yüzey kaplamalarınızı gönderin.