ホーム / 製品 / クリーンルーム機器 / Operating Room Laminar Flow Ceiling 3185 × 3185 mm
STJH-OPERATING-ROOM-LAMINAR-CEILING-3185

Operating Room Laminar Flow Ceiling 3185 × 3185 mm

A large square surgical ceiling designed to cover the operating table and sterile team with low-turbulence H14-filtered airflow.
  • 3185 mm square protected field
  • 9130 m³/h clean airflow
  • Coverage for table and sterile team
見積もりリクエスト 製品案内

商品紹介

With a 3185 x 3185 mm discharge field, this canopy extends protected airflow beyond the operating table to the working positions of the sterile team. The cited clean-air duty is 9130 m³/h with 6000 m³/h recirculation. Its square geometry is suited to general highly aseptic theatres that need more coverage than compact procedural rooms.

主要な特徴

Broader personnel coverage

The expanded square field can encompass the table, instrument area and sterile staff positions.

Balanced recirculation duty

The cited 6000 m³/h recirculation supports the total supply while limiting additional conditioned-air demand.

Modular ceiling integration

Filter and outlet sections can be coordinated around surgical lights and ceiling service penetrations.

技術的なパラメータ

Airflow Field3185 x 3185 mm
Clean Airflow9130 m³/h
Recirculation Airflow6000 m³/h
Final Filter ClassH14
Flow PatternLow-turbulence vertical supply
Protected AreaOperating table and sterile team zone
MountingFlush ceiling integration
Room TypeGeneral highly aseptic theatre
ControlsInterlocked with theatre HVAC operation
カスタマイズ意図したアプリケーションと動作環境に基づいて利用できます。

Applications

For general highly aseptic operating theatres with a multi-person sterile zone. The canopy outline should be coordinated with instrument tables, imaging clearances and air-return placement.

Solutions for Your Application

A compact airflow field leaves sterile team members outside the protected zone.Extend coverage with the 3185 mm square discharge field.
Ceiling lights interrupt uniform air delivery over the table.Coordinate modular filter sections and sealed light interfaces during ceiling design.