Depth-limited HEPA solution
The 150 mm cell provides a traditional separated pack in filter sections that lack room for a 290 mm box.
This 610 × 610 × 150 mm H13 filter uses microglass media folded around aluminum separators. In its standard configuration it delivers 1031 m3/h at a 250 Pa initial resistance; the documented high-capacity selection reaches 1626 m3/h at 350 Pa. Its six-inch box is intended for built-up banks and clean-process AHUs that cannot accept a full-depth separator pack.
The 150 mm cell provides a traditional separated pack in filter sections that lack room for a 290 mm box.
Standard and high-capacity duties allow pressure and airflow to be balanced within the same external size.
Corrugated separators maintain airflow passages through the microglass pack.
| External Dimensions | 610 × 610 × 150 mm |
|---|---|
| Efficiency Class | H13 |
| Filter Medium | Microglass fiber |
| Pleat Separators | Aluminum |
| Standard Airflow | 1031 m3/h |
| Standard Initial Resistance | 250 Pa |
| High-Capacity Airflow | 1626 m3/h |
| High-Capacity Initial Resistance | 350 Pa |
| Housing Depth | 150 mm six-inch class |
| Customization (Özelleşme) | Kullanılan uygulama ve çalışma ortamına göre kullanılabilir. |
Used for final filtration in depth-constrained clean-process AHUs, built-up filter banks and controlled manufacturing supply systems. Airflow selection must match the available fan pressure and the expected loaded-filter operating point.
Specify airflow duty, frame material, gasket location, faceguard and compatible clamping arrangement for the receiving bank.
Bize boyutlarınızı, montaj koşullarınızı, performans hedeflerinizi ve gerekli yüzey kaplamalarınızı gönderin.