หน่วยกรองพัดลมแรงดันสูงแบบคงที่
- Deep Reinforced Pressure Plenum
- Backward-Curved EC Impeller
- Accessible Pressure-Test Port
- Variable-Speed Fan Adjustment
การแนะนําสินค้า
The high-static-pressure fan filter unit combines a backward-curved EC impeller, deep inlet arrangement and reinforced plenum. Formed ribs and corner reinforcement support the casing, while a capped test connection provides access for pressure measurements. The unit is intended for cleanroom selections in which inlet losses or final-filter resistance are important parts of the airflow duty. Pressure capability is evaluated at the required flow, not from the motor size or housing depth alone.
คุณสมบัติที่สําคัญ
Formed ribs and reinforced corners limit casing deflection when the plenum operates at elevated static pressure.
A capped pressure port provides a repeatable connection point for commissioning and maintenance measurements.
Variable EC fan speed provides an adjustment range for balancing the selected fan and filter combination.
โซลูชันสำหรับแอปพลิเคชันของคุณ
A high-resistance duty needs an airflow-and-pressure selection for the complete installation rather than a maximum-pressure figure in isolation.
การใช้งานทั่วไป
พารามิเตอร์ทางเทคนิค
Common reference configuration choices for a pressure-duty ceiling FFU.
| Module-Format Option | Common nominal format: 2 x 4 ft |
|---|---|
| Fan and Drive | Backward-curved centrifugal impeller with variable-speed EC drive |
| Pressure-Plenum Construction | Deep reinforced casing around the fan and final-filter support |
| Reference Face Velocity | Typical selection target: 0.45 m/s through the final-filter face |
| Air-Inlet Options | Open-plenum inlet or duct-collar connection |
| Pressure-Test Connection | Capped static-pressure tapping on the fan plenum |
| Electrical Option | Common supply option: 230 V AC |
| Control-Interface Options | Local speed setting, 0-10 V analogue reference or compatible network controller |
| Final-Filter Configuration | HEPA or ULPA panel selected with the fan duty |
| Perimeter-Seal Options | Dry-gasket compression or matched gel-seal construction |
| การปรับแต่ง | สามารถใช้ได้ตามแอปพลิเคชันที่ตั้งใจไว้และสภาพแวดล้อมการทํางาน |
ตัวเลือกที่มีอยู่
Pressure-Duty Selection and Installation
Define the full resistance path
For a quotation, state the required airflow and external losses at that airflow, including inlet ductwork, fittings and any prefilter. List the final-filter resistance separately so that internal filter pressure drop is not counted twice. The selected fan curve must cover both the clean-filter duty and the intended loaded-filter limit.
Match the inlet and control arrangement
Choose an open intake or a dimensioned duct collar, the final-filter grade, and the gasket or gel-seal construction. An EC motor does not by itself establish constant-airflow operation. Where an upstream air-control device is used, select compatible control behaviour rather than allowing two independent controllers to regulate the same airflow.
Install for measurement and service
Allow access to the test connection, motor controls and filter removal path. Use the specified ceiling support layout and electrical rating, and measure delivered airflow as well as pressure during balancing. Disconnect power before filter or fan maintenance.
A standard fan filter unit may suit a lower-resistance ceiling duty. If the main requirement is increased total volume across a broad outlet, compare the high-airflow fan filter unit.
Planning a High-Static-Pressure Fan Filter Unit specification?
ส่งมิติของคุณเงื่อนไขการติดตั้งเป้าหมายประสิทธิภาพและผิวที่ต้องการ

ภาษาอังกฤษ
ภาษาโปรตุเกส
ภาษาสเปน
ภาษามาเลย์
ภาษาอินโดนีเซีย
ภาษาเยอรมัน
ภาษาตุรกี
ภาษาเวียดนาม
ฝรั่งเศส
ภาษารัสเซีย
ภาษาอาหรับ
ภาษาไทยปัจจุบัน
ภาษาญี่ปุ่น
ภาษาเกาหลี