Maximum standard airflow
The 950 CFM upper limit provides the greatest volume in the non-RSR high-airflow group.
This full-length 24 x 48 in model provides the largest standard airflow range in the accepted high-flow family, from 200 to 950 CFM. It supplies 650 CFM at a 90 FPM reference point and carries a 66 lb housing across a 600 x 1200 x 364 mm envelope. The model suits broad ceiling zones where one module should cover more area and deliver more volume than the 24 x 36 in format.
The 950 CFM upper limit provides the greatest volume in the non-RSR high-airflow group.
A two-by-four-foot cabinet can reduce module count across large production ceiling zones.
The ECM can be commissioned below maximum duty to match the installed filter and room return system.
| Nominal Module Size | 2 x 4 ft |
|---|---|
| External Dimensions | 600 x 1200 x 364 mm |
| Airflow Range | 200-950 CFM |
| Reference Airflow | 650 CFM at 90 FPM |
| Maximum-Airflow Power | 250 W |
| Reference Sound Level | 52 dBA at 90 FPM |
| Motor Type | ECM |
| Unit Weight | 66 lb |
| Installation | Full-perimeter supported 2 x 4 ft ceiling mounting |
| Customisation | Disponible en fonction de l'application prévue et de l'environnement d'exploitation. |
Suitable for high-coverage electronics, pharmaceutical and precision-manufacturing ceilings, especially where the airflow plan favors fewer large modules. The 950 CFM capability must be coordinated with room returns, ceiling support and acceptable sound levels.
Confirm the final-filter grade, ECM control interface, voltage, housing construction and ceiling support. Select the actual airflow from the measured resistance and cleanliness requirement.
Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.