Compact ceiling footprint
The 2.575 m square field fits procedural rooms where lights and services constrain available ceiling area.
The 2575 mm square canopy is sized for operating or procedure rooms where the protected zone must remain compact. At the cited design point it supplies 5970 m³/h of clean air, including 3980 m³/h of recirculation. The smaller field reduces the ceiling footprint while retaining a downward filtered airflow zone over the selected surgical area.
The 2.575 m square field fits procedural rooms where lights and services constrain available ceiling area.
A large share of the design airflow is recirculated locally to reduce the outside-air burden.
Final filtration at the canopy supports clean downward air delivery above the clinical zone.
| Airflow Field | 2575 x 2575 mm |
|---|---|
| Clean Airflow | 5970 m³/h |
| Recirculation Airflow | 3980 m³/h |
| Final Filter Class | H14 |
| Air Distribution | Low-turbulence downward flow |
| Installation | Ceiling-integrated canopy |
| Typical Zone | Compact operating or procedure area |
| Ceiling Coordination | Lights, pendants and services by layout |
| التحكم في تدفق الهواء | Matched to operating-room HVAC design |
| التخصيص | متوفر على أساس التطبيق المقصود وبيئة التشغيل. |
For compact operating theatres and procedure rooms needing a defined ultra-clean field above the table. Air balance, light placement and peripheral return locations are coordinated with the room HVAC design.
Configure filter-module layout, recirculation connection, outlet fabric, lighting interface and service cut-outs. Final airflow follows the clinical risk and HVAC calculations.
أرسل لنا الأبعاد الخاصة بك، شروط التثبيت، أهداف الأداء والتشطيب السطحي المطلوب.