Narrow ceiling integration
The 305 mm width serves perimeter strips and service-congested grid positions without blanking half a full module.
This 305 × 610 × 70 mm H14 panel occupies a half-width terminal opening. It delivers 286 m3/h at a 0.45 m/s face velocity and 145 Pa initial resistance. The narrow form is intended for perimeter zones, corridors and ceiling layouts where lights, sprinklers or structural members prevent use of a full-square HEPA module.
The 305 mm width serves perimeter strips and service-congested grid positions without blanking half a full module.
A 0.45 m/s face velocity provides a documented basis for local airflow and diffuser selection.
The panel maintains H14 final filtration in areas that cannot accept a 610 mm square filter.
| Panel Dimensions | 305 × 610 × 70 mm |
|---|---|
| HEPA Classification | H14 |
| Rated Airflow | 286 m3/h |
| Initial Pressure Drop | 145 Pa |
| Face Velocity | 0.45 m/s |
| Module Width | Half module, 305 mm |
| Pack Depth | 70 mm |
| Terminal Position | Perimeter, corridor or narrow grid |
| Air Distribution | Matched terminal diffuser or housing |
| Tùy chỉnh | Có sẵn dựa trên ứng dụng dự định và môi trường hoạt động. |
Used at cleanroom perimeters, narrow corridors, pass-through approaches and ceiling bays constrained by building services. It allows a fractional terminal layout while providing a defined H14 airflow point for balancing.
Specify gasket or gel edge, frame profile, faceguard and diffuser interface for the 305 × 610 mm ceiling position.
Gửi cho chúng tôi kích thước của bạn, điều kiện lắp đặt, mục tiêu hiệu suất và bề mặt yêu cầu hoàn thiện.