Ihr One-Stop - Lieferant für Reinraumausrüstung und Essentials für aseptische EinrichtungenInternationale Projektunterstützung
Open mobile navigationClose mobile navigation
Startseite / Produkte / Cleanroom Air Filters / Terminal HEPA Filter 305 × 610 × 70 mm H14
STJH-TERMINAL-HEPA-H14-305X610X70

Terminal HEPA Filter 305 × 610 × 70 mm H14

A narrow H14 terminal panel with a documented 286 m3/h duty for perimeter and corridor ceiling grids.
  • 305 × 610 mm half module
  • 286 m3/h rated airflow
  • H14 at 145 Pa initial resistance

Produkteinführung

This 305 × 610 × 70 mm H14 panel occupies a half-width terminal opening. It delivers 286 m3/h at a 0.45 m/s face velocity and 145 Pa initial resistance. The narrow form is intended for perimeter zones, corridors and ceiling layouts where lights, sprinklers or structural members prevent use of a full-square HEPA module.

Key Features

Narrow ceiling integration

The 305 mm width serves perimeter strips and service-congested grid positions without blanking half a full module.

Defined terminal velocity

A 0.45 m/s face velocity provides a documented basis for local airflow and diffuser selection.

H14 fractional coverage

The panel maintains H14 final filtration in areas that cannot accept a 610 mm square filter.

Technische Parameter

Panel Dimensions305 × 610 × 70 mm
HEPA ClassificationH14
Rated Airflow286 m3/h
Initial Pressure Drop145 Pa
Face Velocity0.45 m/s
Module WidthHalf module, 305 mm
Pack Depth70 mm
Terminal PositionPerimeter, corridor or narrow grid
Air DistributionMatched terminal diffuser or housing
CustomisierungVerfügbar je nach beabsichtigter Anwendung und Betriebsumgebung.

Applications

Used at cleanroom perimeters, narrow corridors, pass-through approaches and ceiling bays constrained by building services. It allows a fractional terminal layout while providing a defined H14 airflow point for balancing.

Solutions for Your Application

A full 610 mm module conflicts with ceiling services at the room perimeter.Use the 305 mm-wide terminal panel to preserve filtered coverage in the remaining half bay.
A narrow terminal is overdriven to match a full-module airflow.Balance the panel around its documented 286 m3/h and 0.45 m/s operating point.

Verfügbare Optionen

Specify gasket or gel edge, frame profile, faceguard and diffuser interface for the 305 × 610 mm ceiling position.

Planning a Terminal HEPA Filter 305 × 610 × 70 mm H14 specification?

Senden Sie uns Ihre Abmessungen, Installationsbedingungen, Leistungsziele und gewünschte Oberflächenveredelung.

Sprechen Sie mit unserem Team