Su proveedor de ventanilla única para equipos de sala limpia y elementos esenciales para instalaciones asépticasApoyo a proyectos internacionales
Open mobile navigationClose mobile navigation
Inicio / Productos / Cleanroom HVAC Systems / Electrode Steam Humidifier 91 kg/h Dual-Cylinder
STJH-ELECTRODE-STEAM-HUMIDIFIER-91KGH

Electrode Steam Humidifier 91 kg/h Dual-Cylinder

A high-output two-cylinder cabinet for large clean facilities or two independently controlled steam duties.
  • 9-91 kg/h total output
  • Two cylinders and circuits
  • 74.8 kW maximum input
Solicite un presupuesto. Browse productos

Introducción del producto

The 91 kg/h cabinet contains two independent steam cylinders and two control circuits, with maximum electrical input of 74.8 kW. The dual arrangement increases output beyond the single-cylinder range and can support two-zone delivery or staged capacity. Water conductivity, electrical load and steam-distribution geometry must be checked for both circuits so the large unit does not simply transfer a sizing problem to the duct.

Características clave

Dual steam generation

Two cylinders expand total capacity and provide staged operation across a wider load range.

Two control circuits

Independent control sections can serve separated distribution duties when configured accordingly.

Large-facility package

One enclosure concentrates high steam output for central cleanroom air systems.

Parámetros técnicos

Steam Output9-91 kg/h
Maximum Input74.8 kW
Steam Cylinders2
Control Circuits2
Heating PrincipleElectrode boiling
Electrical SupplyThree-phase by selected voltage
Feed WaterConductive potable water
DistributionOne or two steam delivery circuits by design
Primary DutyLarge clean-facility humidification
CustomizationDisponible según la aplicación prevista y el entorno operativo.

Applications

For large clean manufacturing AHUs, hospital systems and two-zone steam distribution requiring up to 91 kg/h.

Solutions for Your Application

Both cylinders start together and create an unacceptable electrical demand step.Sequence the two circuits and coordinate demand limiting with the facility electrical controls.
Unequal zone loads cause one cylinder to age much faster than the other.Use independent demand signals or rotate lead duty where the distribution design permits it.

Opciones disponibles

Confirm total and zone steam loads, voltage, cylinder control, water conductivity, dual manifolds, hose routing, drainage and BMS interface.

Planning a Electrode Steam Humidifier 91 kg/h Dual-Cylinder specification?

Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.