클린룸 장비 및 무균 시설 필수품의 원스톱 공급업체국제 프로젝트 지원
Open mobile navigationClose mobile navigation
/ 제품 / Cleanroom Air Filters / Side-Access HEPA Filter Housing Two-Wide
STJH-SIDE-ACCESS-HEPA-HOUSING-2W

Side-Access HEPA Filter Housing Two-Wide

A parallel two-cell HEPA cabinet for medium-flow clean air systems needing service access from either side.
  • Two parallel HEPA cells
  • About 4000 cfm design basis
  • Galvanized or 304 stainless
견적 요청 제품 찾아보기

상품 소개

This two-wide housing places two full-size HEPA filters in parallel across an approximately 52 in cabinet width. At a 500 fpm face-velocity basis, the arrangement supports about 4000 cfm and reduces resistance compared with forcing the same flow through one cell. Galvanized or 304 stainless construction can be selected, and removable doors on both sides preserve service flexibility in congested mechanical rooms.

주요 기능

Doubled active face

Two filters share the airflow, supporting medium AHU duty without stacking cells vertically.

Independent clamping

Each filter position receives its own sealing force so one replacement does not disturb the adjacent cell.

Dual-side maintenance

Removable doors on both cabinet sides allow the service plan to follow actual plant access.

기술 매개변수

Filter CapacityTwo full-size HEPA filters wide
Housing Material14-gauge galvanized or 304 stainless steel
AccessDual-side removable doors
Family Pressure CapabilityUp to ±8 in. w.g.
Rated Airflow BasisAbout 4000 cfm at 500 fpm face velocity
Filter SealIndividual mechanical compression
Prefilter TrackOptional nominal 2 in track
Cabinet WidthApproximately 52 in class
InstallationMedium-flow ducted filter section
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

Applications

For medium-flow cleanroom air handlers, hospital supply systems and controlled manufacturing ventilation using two full-size final filters in one row.

Solutions for Your Application

The two filters receive unequal flow because the upstream transition is too short.Provide a distribution plenum or gradual transition and confirm comparable velocity at both filter faces.
The wider cabinet leaves no clear path to withdraw a full-size filter.Reserve the complete door swing and filter pull envelope on at least one side before fixing nearby services.

사용 가능한 옵션

Confirm cabinet alloy, filter depth, gasket layout, clamping style, active service side, prefilter track, ports and duct transition dimensions.

Planning a Side-Access HEPA Filter Housing Two-Wide specification?

치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.