Doubled active face
Two filters share the airflow, supporting medium AHU duty without stacking cells vertically.
This two-wide housing places two full-size HEPA filters in parallel across an approximately 52 in cabinet width. At a 500 fpm face-velocity basis, the arrangement supports about 4000 cfm and reduces resistance compared with forcing the same flow through one cell. Galvanized or 304 stainless construction can be selected, and removable doors on both sides preserve service flexibility in congested mechanical rooms.
Two filters share the airflow, supporting medium AHU duty without stacking cells vertically.
Each filter position receives its own sealing force so one replacement does not disturb the adjacent cell.
Removable doors on both cabinet sides allow the service plan to follow actual plant access.
| Filter Capacity | Two full-size HEPA filters wide |
|---|---|
| Housing Material | 14-gauge galvanized or 304 stainless steel |
| Access | Dual-side removable doors |
| Family Pressure Capability | Up to ±8 in. w.g. |
| Rated Airflow Basis | About 4000 cfm at 500 fpm face velocity |
| Filter Seal | Individual mechanical compression |
| Prefilter Track | Optional nominal 2 in track |
| Cabinet Width | Approximately 52 in class |
| Installation | Medium-flow ducted filter section |
| التخصيص | متوفر على أساس التطبيق المقصود وبيئة التشغيل. |
For medium-flow cleanroom air handlers, hospital supply systems and controlled manufacturing ventilation using two full-size final filters in one row.
Confirm cabinet alloy, filter depth, gasket layout, clamping style, active service side, prefilter track, ports and duct transition dimensions.
أرسل لنا الأبعاد الخاصة بك، شروط التثبيت، أهداف الأداء والتشطيب السطحي المطلوب.