Intermediate airflow capacity
The 2600 m3/h rating covers medium ductwork between the compact and high-volume configurations.
This 18 W version extends the active section to 371 mm and raises the supported airflow to 2600 m3/h. It gives medium AHUs more treatment length than the compact 10 W model without the installation envelope of the 28 W unit. Airflow sensing, digital lamp-life indication and alarm ports support planned maintenance, while pollutant reduction remains dependent on the actual contaminant, contact conditions and a clean photocatalytic surface.
The 2600 m3/h rating covers medium ductwork between the compact and high-volume configurations.
A 371 mm section increases illuminated photocatalyst area compared with the 10 W module.
Alarm and control terminals allow lamp and airflow status to be integrated with the air-system controls.
| Electrical Power | 18 W |
|---|---|
| Supply | 220-240 V, 50/60 Hz |
| Rated Current | 0.095 A |
| Overall Dimensions | 250 x 157 x 443 mm |
| Treatment Section Length | 371 mm |
| Maximum Airflow | 2600 m3/h |
| Ingress Protection | IP20 |
| Treatment Method | UV-C activated TiO2 photocatalysis |
| Controls | Airflow sensor, digital life display and alarm ports |
| 사용자 정의 | 의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다. |
Suited to medium cleanroom make-up or recirculation branches, commercial AHUs and controlled-process ventilation requiring a monitored PCO stage.
Select mounting orientation, duct penetration, control wiring, alarm logic, upstream filter grade and service interval for the actual air stream.
치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.