클린룸 장비 및 무균 시설 필수품의 원스톱 공급업체국제 프로젝트 지원
Open mobile navigationClose mobile navigation
/ 제품 / 클린룸 장비 / Equipment Fan Filter Unit 2 × 4 ft
STJH-EQUIPMENT-FAN-FILTER-UNIT-2X4

Equipment Fan Filter Unit 2 × 4 ft

A slim, high-pressure equipment FFU for stockers, narrow tools and compact mini-environments.
  • 575 x 1175 mm footprint
  • 360 Pa static pressure
  • H14 filter, 50 mm deep
견적 요청 제품 찾아보기

상품 소개

This 2 x 4 equipment fan filter unit uses a 575 x 1175 mm footprint and a slim 110 + 35 mm cabinet arrangement. It provides the highest listed static pressure in the three-model EFU group at 360 Pa, while retaining the lowest 60-95 W power band. A 50 mm H14 filter supports direct integration into semiconductor stockers and narrow tool enclosures.

주요 기능

Slim tool-top package

The low cabinet profile limits intrusion into compact equipment and mini-environment service zones.

Pressure-priority duty

The 360 Pa value gives this size the greatest resistance capability in the accepted EFU group.

Low power band

A listed 60-95 W range supports efficient localized clean-air supply.

기술 매개변수

Nominal Format2 x 4
Footprint575 x 1175 mm
Cabinet Height110 + 35 mm
Static Pressure360 Pa
Power Input60-95 W
Sound Level44-48 dBA
Final FilterH14, 50 mm
InstallationEquipment-roof or mini-environment mounting
Airflow DirectionFiltered supply into the tool enclosure
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

Applications

Designed for semiconductor stockers, compact tool enclosures and narrow mini-environments that need pressure reserve in a shallow package. Final duty should be confirmed against tool resistance and leakage.

Solutions for Your Application

The equipment roof cannot accept a conventional deep FFU.Use the slim 110 + 35 mm cabinet arrangement over the 575 x 1175 mm opening.
Tool resistance reduces airflow from a standard low-pressure module.Select the 360 Pa EFU and commission it against the complete enclosure pressure loss.

사용 가능한 옵션

Confirm electrical supply, speed control, H14 seal, equipment opening and service direction. The final fan setting should reflect actual tool resistance.