Single-position protection
The compact field concentrates clean supply air over one patient or clinical work location.
The 1355 mm square ward ceiling supplies a cited 1660 m³/h through a polyester-cloth outlet, creating a localized low-turbulence air zone over one bed or treatment position. Its compact footprint minimizes interference with luminaires, medical rails and ceiling services. The model is intended for targeted patient protection rather than full-room unidirectional coverage.
The compact field concentrates clean supply air over one patient or clinical work location.
A polyester-cloth outlet spreads the H14-filtered air with low turbulence at the occupied zone.
The smaller square leaves more ceiling area for lights, rails and medical utilities.
| Outlet Field | 1355 x 1355 mm |
|---|---|
| Clean Airflow | 1660 m³/h |
| Final Filter Class | H14 |
| Outlet Material | Polyester cloth |
| Flow Character | Low-turbulence downward supply |
| Coverage | One patient or treatment position |
| Installation | Ceiling integrated |
| Plenum Construction | Project-selected cleanroom material |
| 공기 흐름 제어 | Matched to ward pressure and ventilation plan |
| 사용자 정의 | 의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다. |
For a single protective-environment bed, isolation-room care point or clinical treatment station needing localized H14-filtered supply air.
Configure plenum material, filter access, suspension, outlet cloth, airflow monitoring and ceiling-service coordination. Final duty is balanced with room pressure requirements.
치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.