A broad-face 24 VDC HEPA supply module for covered transfer sections and larger local clean-air zones.
  • Broad-face HEPA supply module
  • 480 mm square outlet
  • Covered transfer sections
見積もりリクエスト 製品案内

商品紹介

This format uses a 450 mm square filter element beneath the fan chamber, giving the series its widest discharge face. A 150 mm-high body keeps the assembly shallow relative to its span. The 514 x 520 mm nominal size refers to a casing measuring 514 x 519.5 mm, with space also needed around its electrical connection.

主要な特徴

480 mm square outlet

The 480 mm square outlet spreads supply air across a broader opening.

Five fan positions

Five fan positions let the operator reduce output when the full transfer zone is not in use.

Four mounting points

Four mounting points support integration over a hood without relying on the filter frame to carry the assembly.

技術的なパラメータ

Casing Dimensions514 W x 519.5 D x 150 H mm
Power Supply24 VDC
Motor TypeBrushless DC motor
Airflow SettingsFive steps: approximately 5.3 / 4.5 / 3.3 / 2.2 / 1.1 m³/min
Nominal Discharge VelocityApproximately 0.46 / 0.39 / 0.29 / 0.19 / 0.10 m/s in descending airflow order
Power ConsumptionApproximately 48 / 35 / 23 / 15 / 8 W across the five positions
Main FilterHEPA, 450 x 450 x 50 mm; nominal particle collection efficiency at least 99.99% at 0.3 µm
PrefilterAccessible mesh screen upstream of the fan
Casing MaterialAntistatic ABS housing
カスタマイズHood attachment and power-lead routing can be configured for the intended transfer process and operating environment.

Applications

Clean-air supply above a covered conveyor transfer point. A wider local canopy for exposed component trays between process steps.

Solutions for Your Application

A narrow air outlet may leave the edges of a broad tray outside the supplied area.Position the wider outlet over the exposed region and assess edge airflow with the intended tray and hood geometry.
Increasing fan output alone can create excessive local air speed.Use the larger discharge area to distribute the flow, then select a fan position appropriate to the uncovered product and nearby openings.

利用可能なオプション

A higher-efficiency ULPA filter selection for sensitive transfer processes. A suitable 24 VDC connection cable for integration with machine wiring.