クリーンルーム機器と無菌施設の必需品のワンストップサプライヤー国際プロジェクト支援
Open mobile navigationClose mobile navigation
ホーム / 製品 / Cleanroom Air Filters / High-Airflow Medium-Efficiency Filter 1800 m3/h Half-Module
STJH-HIGH-AIRFLOW-MEDIUM-FILTER-1800

High-Airflow Medium-Efficiency Filter 1800 m3/h Half-Module

A narrow E10 V-bank module for 1800 m3/h process-air duty at operating temperatures up to 120 °C.
  • 610 × 305 mm half module
  • E10 filtration
  • 120 °C maximum temperature
見積もりリクエスト 製品案内

商品紹介

This 610 × 305 × 292 mm E10 compact filter is the half-module member of the high-temperature airflow family. Its narrow face handles 1800 m3/h with a published 190 Pa initial pressure drop and is designed for temperatures up to 120 °C. The size is suited to constrained process-air banks and support ventilation near thermal or sterilization operations.

主要な特徴

Narrow high-temperature module

The 305 mm width fits split banks while the construction supports elevated process-air temperature.

Defined half-module airflow

A nominal 1800 m3/h rating allows the filter to be combined predictably in modular arrays.

Compact E10 pack

The 292 mm V-bank depth provides high media area without long pockets in heated airflow.

技術的なパラメータ

Overall Dimensions610 × 305 × 292 mm
Filter ClassE10
Nominal Airflow1800 m3/h
Initial Pressure Drop190 Pa
Maximum Operating Temperature120 °C
Module FormatHalf-width high-airflow cassette
Nominal Depth292 mm
Media ArrangementCompact V-bank packs
Primary DutyHeated process supply or recirculation air
カスタマイズ意図したアプリケーションと動作環境に基づいて利用できます。

Applications

Designed for narrow process-air systems, sterilization support ventilation and heated clean manufacturing supply where E10 filtration is appropriate. Multiple half modules can be arranged around fixed equipment or nonstandard bank geometry.

Solutions for Your Application

A full-size filter cannot fit around process equipment inside the air handler.The 305 mm half-module width provides a modular high-temperature E10 option for the remaining bay.
Normal HVAC filters may not tolerate the specified warm-air duty.Use this construction within its 120 °C maximum operating temperature and verify the complete system temperature profile.

利用可能なオプション

Confirm high-temperature gasket, header style, installation orientation and exact operating temperature before ordering.

Planning a High-Airflow Medium-Efficiency Filter 1800 m3/h Half-Module specification?

寸法、設置条件、性能目標、必要な表面仕上げをお送りください。

チームに相談する
メール送信 WhatsApp WeChat

ホーム

製品

ニュース

会社概要

お問い合わせ