Heavy filled-steel body
The formed bottom pan and top sheet are welded around structural features and the perimeter, enclosing the cementitious core beneath the usable floor surface.
The HD25 arrangement combines a welded steel panel and structural cementitious fill with 4 ft bolted stringers in a basketweave layout. Its reference design duty is 2,500 lb, with a 2,000 lb rolling criterion at 10,000 passes. The support arrangement is part of the model's identity: selecting the same panel with different stringers changes the complete system configuration.
The formed bottom pan and top sheet are welded around structural features and the perimeter, enclosing the cementitious core beneath the usable floor surface.
The basketweave arrangement defines how loads reach the pedestals. Retain the matched supports when comparing this configuration with deeper-stringer alternatives in the same panel family.
Repeated load capability helps define transport routes for dense cabinets and mobile equipment, but wheel positions and contact geometry must still be considered at thresholds and turns.
| Module Size | 24 x 24 in (609.6 x 609.6 mm) |
|---|---|
| Shell Material | Welded steel |
| Core Fill | Structural cementitious material |
| Protective Finish | Epoxy paint |
| Reference Design Load | 2,500 lb |
| Reference Ultimate Load | 5,000 lb |
| Rolling Load at 10,000 Passes | 2,000 lb |
| Stringer Arrangement | 4 ft bolted basketweave system |
| Reference System Weight | 63.5 kg/m² |
| カスタマイズ | 意図したアプリケーションと動作環境に基づいて利用できます。 |
Suitable for equipment-intensive technical suites, process-support rooms and test areas with substantial repeated rolling traffic. The quoted duty describes the matched reference configuration, not an unsupported panel placed on arbitrary pedestals. Plan cabinet feet and transport routes with service openings so future cuts do not remove support where the highest loads occur.
Select the repeated rolling-duty configuration and compare actual wheel loads with the relevant transport case.
Keep the basketweave support arrangement defined in the order so the load path remains consistent with the selected system.
Specify the surface covering, floor height and service apertures. Where heavier duty is required, evaluate a complete deeper-stringer configuration instead of assuming a finish change increases structural capacity.
寸法、設置条件、性能目標、必要な表面仕上げをお送りください。