STJH-BACKDRAFT-DAMPER-VERTICAL-INTAKE

Backdraft Damper Vertical-Mount Intake

A gravity-operated intake damper for vertical wall or duct openings.
  • The intake flange establishes a clear mounting side.
  • Light blades provide passive operation for normal ventilation duty.
見積もりリクエスト 製品案内

商品紹介

The intake-side flange seats against the entering-air side of the opening. Horizontal airflow lifts the aluminum blades away from their stops; the vertical installation lets them settle closed when forward flow is lost.

主要な特徴

  • The intake flange establishes a clear mounting side.
  • Light blades provide passive operation for normal ventilation duty.

技術的なパラメータ

InstallationVertical
Airflow DirectionHorizontal intake
Flange PositionIntake side
FrameGalvanized steel
BladesAluminum
Return MechanismGravity closing
Typical Opening PressureApproximately 0.009 in. w.g.; varies with size
Maximum Air Velocity1500 fpm
Reverse Pressure Limit2 in. w.g.
カスタマイズAvailable to match the intake opening and operating conditions.

Applications

  • Ventilation intake plenums
  • Vertical branch intake openings

Solutions for Your Application

The intake flange could be installed on the wrong face.

Use the incoming-air flange as the seating face and preserve the blade opening direction.

Reverse airflow occurs when the supply fan stops.

The freely pivoting blades fall onto their closing stops without a control signal.