クリーンルーム機器と無菌施設の必需品のワンストップサプライヤー国際プロジェクト支援
Open mobile navigationClose mobile navigation
ホーム / 製品 / Air Ducts & Air Distribution / Backdraft Damper Vertical-Mount Discharge
STJH-BACKDRAFT-DAMPER-VERTICAL-DISCHARGE

Backdraft Damper Vertical-Mount Discharge

Automatic reverse-flow prevention at a horizontal exhaust outlet.
  • Outlet-side fixing supports sidewall discharge layouts.
  • Separate blades allow the opening to respond directly to exhaust flow.
見積もりリクエスト 製品案内

商品紹介

This vertical damper locates its fixing flange on the discharge side. Forward exhaust pushes the blades outward, while the hanging arrangement closes the opening when the fan stops. The flange orientation suits outlet-side seating.

主要な特徴

  • Outlet-side fixing supports sidewall discharge layouts.
  • Separate blades allow the opening to respond directly to exhaust flow.

技術的なパラメータ

Mounting OrientationVertical
Design Flow DirectionHorizontal discharge
Mounting FlangeDischarge side
Frame ConstructionGalvanized steel
Blade ConstructionAluminum
OperationAir-pressure opening, gravity closure
Start-Open PressureApproximately 0.009 in. w.g., depending on dimensions
Velocity Limit1500 fpm
Back Pressure Limit2 in. w.g.
カスタマイズAvailable for the selected exhaust outlet and installation geometry.

Applications

  • Sidewall exhaust outlets
  • Horizontal in-duct discharge points

Solutions for Your Application

Wind drives air back into an idle exhaust branch.

Closing blades interrupt the reverse path after forward flow falls away.

Only the outlet face is available for fixing.

The discharge flange presents the mounting edge on that side of the frame.

利用可能なオプション

  • Outlet dimensions
  • Fixing flange arrangement

Planning a Backdraft Damper Vertical-Mount Discharge specification?

寸法、設置条件、性能目標、必要な表面仕上げをお送りください。

チームに相談する