Wind drives air back into an idle exhaust branch.
Closing blades interrupt the reverse path after forward flow falls away.
This vertical damper locates its fixing flange on the discharge side. Forward exhaust pushes the blades outward, while the hanging arrangement closes the opening when the fan stops. The flange orientation suits outlet-side seating.
| Mounting Orientation | Vertical |
|---|---|
| Design Flow Direction | Horizontal discharge |
| Mounting Flange | Discharge side |
| Frame Construction | Galvanized steel |
| Blade Construction | Aluminum |
| Operation | Air-pressure opening, gravity closure |
| Start-Open Pressure | Approximately 0.009 in. w.g., depending on dimensions |
| Velocity Limit | 1500 fpm |
| Back Pressure Limit | 2 in. w.g. |
| Customization | Available for the selected exhaust outlet and installation geometry. |
Closing blades interrupt the reverse path after forward flow falls away.
The discharge flange presents the mounting edge on that side of the frame.