A small branch can receive excessive air when system pressure rises.
Closed-loop regulation changes blade position as measured flow departs from the setpoint.
A short round casing houses a pressure pickup and rotating blade. The external control assembly compares measured flow with a room demand signal and adjusts the opening, making the unit suitable for branches where a fixed balancing setting cannot follow changing use.
| Nominal Diameter | 100 mm |
|---|---|
| Casing Material | Galvanized steel |
| Control Method | Electronic modulation |
| Flow Measurement | Differential-pressure pickup |
| Dynamic Control Range | Approximately 10–100% of nominal flow |
| Maximum Differential Pressure | 1000 Pa |
| Operating Temperature | 10–50 °C |
| Supply Voltage | 24 V AC/DC with electronic controller |
| Control Signal | 0–10 V DC controller option |
| Customization (Kustomisasi) | Available for the intended room duty and operating environment. |
Closed-loop regulation changes blade position as measured flow departs from the setpoint.
The compact circular body connects directly to the small round branch.
Kirimkan kami dimensi Anda, kondisi instalasi, target kinerja dan permukaan akhir yang diperlukan.