A small branch can receive excessive air when system pressure rises.
Closed-loop regulation changes blade position as measured flow departs from the setpoint.
A short round casing houses a pressure pickup and rotating blade. The external control assembly compares measured flow with a room demand signal and adjusts the opening, making the unit suitable for branches where a fixed balancing setting cannot follow changing use.
| Nominal Diameter | 100 mm |
|---|---|
| Casing Material | Galvanized steel |
| Control Method | Electronic modulation |
| Flow Measurement | Differential-pressure pickup |
| Dynamic Control Range | Approximately 10–100% of nominal flow |
| Maximum Differential Pressure | 1000 Pa |
| Operating Temperature | 10–50 °C |
| Supply Voltage | 24 V AC/DC with electronic controller |
| Control Signal | 0–10 V DC controller option |
| Customisation | Available for the intended room duty and operating environment. |
Closed-loop regulation changes blade position as measured flow departs from the setpoint.
The compact circular body connects directly to the small round branch.
Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.