A medium forty-six-element boiler for central clean-facility heating with substantially greater flow than the compact unit.
  • 920 kW maximum input
  • Forty-six elements
  • 680 gpm maximum flow
Demander un devis. Browse les produits

Introduction de produit

The 920 kW package expands vessel diameter to 24 in and uses forty-six electric elements. A 6 in flanged outlet and up to 680 gpm documented flow distinguish its hydraulic hardware from the 280 kW model. The medium unit suits pharmaceutical or electronics facilities with several heating coils, provided electrical distribution, pump head and element staging are coordinated with the actual diversity of the hot-water load.

Key Features

Central plant capacity

The larger vessel and element bank serve multiple AHU coils from one electric hot-water source.

High-flow connections

A 6 in flanged outlet supports the documented medium-plant circulation rate.

Sequenced electric output

Forty-six elements provide multiple control steps for varying facility demand.

Paramètres techniques

Maximum Input920 kW
Vessel Diameter24 in
Element Count46
Maximum Flow680 gpm
Outlet Connection6 in flanged
Heating MethodElectric immersion elements
System DutyCentral hot-water heating
Flow ControlExternal circulation pump
Electrical ControlMulti-stage package by selection
CustomisationDisponible en fonction de l'application prévue et de l'environnement d'exploitation.

Applications

For medium pharmaceutical, electronics and controlled-production buildings with centralized hot-water heating and reheat demand.

Solutions for Your Application

Demand steps cause large electrical peaks when too many elements energize together.Use staged sequencing and demand limits coordinated with the facility electrical system.
A 680 gpm pump selection creates excessive velocity at part load.Select variable flow, bypass and minimum boiler circulation from the real coil diversity and vessel requirements.

Options disponibles

Specify supply voltage, staging, outlet arrangement, water temperature, pumps, expansion vessel, safety controls and communication interface.

Planning a Packaged Electric Hot-Water Boiler 920 kW specification?

Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.

Parlez à notre équipe
Email nous WhatsApp WeChat

Accueil

Produits

Actualités

À propos

Contact