Seu fornecedor único para equipamentos de sala limpa e instalações assépticas essenciaisApoio Internacional a Projetos
Open mobile navigationClose mobile navigation
Início / Produtos / Cleanroom HVAC Systems / Packaged Electric Hot-Water Boiler 920 kW
STJH-PACKAGED-ELECTRIC-HOT-WATER-BOILER-920KW

Packaged Electric Hot-Water Boiler 920 kW

A medium forty-six-element boiler for central clean-facility heating with substantially greater flow than the compact unit.
  • 920 kW maximum input
  • Forty-six elements
  • 680 gpm maximum flow
Solicite um orçamento. Browse produtos

Introdução do produto

The 920 kW package expands vessel diameter to 24 in and uses forty-six electric elements. A 6 in flanged outlet and up to 680 gpm documented flow distinguish its hydraulic hardware from the 280 kW model. The medium unit suits pharmaceutical or electronics facilities with several heating coils, provided electrical distribution, pump head and element staging are coordinated with the actual diversity of the hot-water load.

Características-chave

Central plant capacity

The larger vessel and element bank serve multiple AHU coils from one electric hot-water source.

High-flow connections

A 6 in flanged outlet supports the documented medium-plant circulation rate.

Sequenced electric output

Forty-six elements provide multiple control steps for varying facility demand.

Parâmetros técnicos

Maximum Input920 kW
Vessel Diameter24 in
Element Count46
Maximum Flow680 gpm
Outlet Connection6 in flanged
Heating MethodElectric immersion elements
System DutyCentral hot-water heating
Flow ControlExternal circulation pump
Electrical ControlMulti-stage package by selection
CustomizaçãoDisponível com base na aplicação pretendida e no ambiente operacional.

Applications

For medium pharmaceutical, electronics and controlled-production buildings with centralized hot-water heating and reheat demand.

Solutions for Your Application

Demand steps cause large electrical peaks when too many elements energize together.Use staged sequencing and demand limits coordinated with the facility electrical system.
A 680 gpm pump selection creates excessive velocity at part load.Select variable flow, bypass and minimum boiler circulation from the real coil diversity and vessel requirements.

Opções disponíveis

Specify supply voltage, staging, outlet arrangement, water temperature, pumps, expansion vessel, safety controls and communication interface.

Planning a Packaged Electric Hot-Water Boiler 920 kW specification?

Envie-nos as suas dimensões, condições de instalação, metas de desempenho e acabamento de superfície necessário.

Fale com a nossa equipe
Email-nos O WhatsApp WeChat

Início

Produtos

Notícias

Sobre nós

Contato