Low-bypass fluid path
The continuous gel channel conforms around the mating knife edge and can reveal discontinuities through its impression.
The gel-seal ePTFE model places a continuous fluid channel in the anodized aluminum perimeter. A housing knife edge enters the gel when the panel is raised into a bottom-load terminal, while the supported membrane provides H14 efficiency, low outgassing and high tensile strength. This arrangement is distinct from the gasket model because sealing depends on knife-edge immersion rather than clamp compression.
The continuous gel channel conforms around the mating knife edge and can reveal discontinuities through its impression.
Supported ePTFE reduces the risk of incidental handling damage during room-side replacement.
The bottom-load format allows filter changeout without opening a common plenum above the room.
| HEPA Class | H14 / at least 99.995% at MPPS |
|---|---|
| Filter Medium | Supported ePTFE membrane |
| Perimeter Frame | Anodized aluminum |
| Seal Configuration | Integral low-outgassing gel channel |
| Mating Component | Knife edge on terminal housing |
| Media Characteristics | Low pressure drop and high tensile strength |
| Environmental Property | Hydrophobic membrane surface |
| Access Mode | Room-side or bottom-load replacement |
| Service Check | Inspect gel surface and knife-edge impression |
| التخصيص | متوفر على أساس التطبيق المقصود وبيئة التشغيل. |
Selected for aseptic pharmaceutical terminals, biotechnology rooms and controlled filling areas with a housing knife edge and room-side access. It is useful when a fluid seal and durable membrane media are both required, provided gel chemistry is compatible with the sanitation program.
Choose gel material, channel dimensions, exact frame size, upstream screen and room-side retaining hardware for the terminal.