Gentle final-stage heating
Low surface loading supports controlled air-temperature trim without concentrating heat on a few elements.
This final-stage heater spreads 20 kW across 24 finned elements on an eight-inch flange. The low 3 W/in2 loading moderates element surface temperature for sensitive clean process air and downstream temperature trim.
Low surface loading supports controlled air-temperature trim without concentrating heat on a few elements.
Twenty-four elements spread output across the flow path for more even heat input.
The assembly bolts into a matching duct or circulation-heater housing as a removable stage.
| Heating Capacity | 20 kW |
|---|---|
| Flange Size | 8 in |
| Element Count | 24 |
| Watt Density | 3 W/in2 |
| Element Type | Finned electric elements |
| Heating Role | Low-density final stage |
| Airflow Requirement | Continuous proven airflow during heating |
| Control | Staged or modulating power option |
| Installation | Flanged duct or circulation housing |
| Tùy chỉnh | Voltage, controls and element sheath can be configured for the intended application and operating environment. |
Sensitive clean process-air trim, final duct heating, controlled drying air and low-surface-temperature air systems.
Sheath alloy, supply voltage, power stages, SCR control, airflow switch, high-limit sensors and terminal enclosure can be selected.
Gửi cho chúng tôi kích thước của bạn, điều kiện lắp đặt, mục tiêu hiệu suất và bề mặt yêu cầu hoàn thiện.