A wide low-profile wall purifier combining two-stage HEPA filtration with two internal UV-C lamps.
  • 400-450 CFM clean airflow
  • Two 36 W UV-C lamps
  • Wall or ceiling mounting
Alıntı isteği Browse ürünleri

Ürün tanıtımı

This 40 in wide anodized-aluminium purifier mounts on a wall or ceiling to preserve floor area. It delivers 400-450 CFM through a MERV 8 prefilter and HEPA final stage, with two ozone-free 36 W UV-C lamps inside the recirculating cabinet. Front-panel filter access and standard 120 V input suit smaller preparation and support rooms.

Ana Özellikler

Floor-space-free installation

The 16 x 40 x 15 in housing mounts above occupied surfaces rather than using a mobile base.

Internal UV-C treatment

Two ozone-free lamps operate within the filter cabinet instead of exposing the room directly.

Front filter access

The MERV 8 and HEPA stages can be reached from the room side of the installed purifier.

Teknik parametreler

External Dimensions40 W x 15 D x 16 H in
Clean Airflow400-450 CFM
Housing16-gauge anodized aluminium
PrefilterMERV 8 disposable pleated filter
Final FilterHEPA; ULPA optional
UV-C Lamps2 x 36 W, ozone-free
Power Supply120 V AC, 50/60 Hz, 1.8 A
Impeller Fan225 W
MountingWall or ceiling
Customization (Özelleşme)Kullanılan uygulama ve çalışma ortamına göre kullanılabilir.

Applications

Suitable for pharmacy support rooms, gowning areas, dental or healthcare preparation rooms and small controlled spaces with limited floor area. UV-C lamp access and replacement intervals should be incorporated into maintenance planning.

Solutions for Your Application

A mobile purifier obstructs an already crowded floor.Mount the 15 in deep cabinet on a suitable wall or ceiling while retaining front service clearance.
Operators need particle filtration and an internal irradiation stage in one unit.Use the MERV 8/HEPA train with the two enclosed ozone-free UV-C lamps.

Mevcut Seçenekler

Available choices include ULPA filtration, 304 or 316L stainless construction, inlet or outlet duct collar, 220 V fan and illuminated filter-change indication.

Planning a Wall-Mounted HEPA Air Purifier 400 CFM UV-C specification?

Bize boyutlarınızı, montaj koşullarınızı, performans hedeflerinizi ve gerekli yüzey kaplamalarınızı gönderin.