An on-off motor cannot hold intermediate damper positions.
The analog command determines a proportional shaft position.
The compact rotary drive clamps to a damper shaft and follows an analog position command. This 10 Nm selection is configured for a 150-second stroke, allowing gradual positioning where a power-loss return action is not required.
| Torque | 10 Nm |
|---|---|
| Supply | 24 V AC/DC |
| Control Signal | 2–10 V DC |
| Fail-Safe Function | Non fail-safe |
| Rotation Angle | 95 degrees |
| Configured Running Time | 150 s per 90 degrees |
| Running Power | 2.5 W |
| Holding Power | 0.4 W |
| Ambient Temperature | -30 to 50 °C |
| การปรับแต่ง | Available for the damper shaft, control sequence and operating environment. |
The analog command determines a proportional shaft position.
The configured 150-second stroke provides a slower positioning option.
ส่งมิติของคุณเงื่อนไขการติดตั้งเป้าหมายประสิทธิภาพและผิวที่ต้องการ