Cleanroom HEPA Supply Air Terminal 610 x 610 mm Ultra-Thin 600 m³/h
- Square compact module fits local terminal filtration points.
- Low body depth preserves space above the ceiling.
Terminal filtration where ceiling depth is restricted
The nominal 610 x 610 x 150 mm module combines an aluminum perimeter, glass-fibre pleated filter pack and steel duct-connection plate. Air is supplied by the upstream system; there is no integral fan. The shallow body can suit a local ceiling supply point, but the complete installation envelope must also include the inlet, duct bend, supports, sealing detail and service access.
Separate the product name from the filter evidence
The previous efficiency entry of at least 99.9% at 0.3 µm is insufficient evidence of a HEPA classification. For a HEPA duty, require the applicable test standard, selected filter class, test airflow and identified filter report. Do not reinterpret that single percentage as H13, H14 or an installed-system leakage result. The filter's particle efficiency also does not establish a cleanroom class.
| Item | Reference configuration |
|---|---|
| Outside body | 610 x 610 x 150 mm nominal; not the required ceiling cut-out or total installation depth. |
| Airflow duty | 600 m³/h listed reference; confirm the selected element and assembly at this operating point. |
| Initial resistance | Up to 120 Pa listed, subject to a report defining test flow and whether housing and outlet losses are included. |
| Materials | Aluminum profile frame, steel top plate, glass-fibre media and hot-melt pleat spacers as listed. |
| Temperature | 80 °C was listed as a maximum; treat as unverified until the complete media, adhesive, seal and frame configuration is approved for the exposure. |
Available pressure and filter replacement
The upstream fan must overcome branch, balancing-device and terminal resistance, including the selected service condition of the filter. A clean-filter pressure value is not the whole pressure budget. Provide pressure measurement access so operating changes can be distinguished from a loaded filter.
Establish whether the filter is separately replaceable or the complete module is replaced; the shallow appearance does not answer that question. The chosen replacement route determines clearance below or above the ceiling, removable faces and duct disconnection access. Support the unit without loading the media or distorting its sealing perimeter.
Testing, cleaning and the purchase schedule
Plan upstream challenge-aerosol access, sampling and downstream inspection with the selected leakage-test method. A filter factory report and an installed leakage test address different questions. An apparently clean face or a normal pressure reading cannot demonstrate an intact seal.
Clean accessible housing surfaces without wetting or brushing fragile filter media. Replace damaged elements using the approved procedure and release testing. State airflow, filter class, inlet position, ceiling interface, test ports, suspension, outlet face and replacement scope in the inquiry. Price these items and commissioning explicitly. Acceptance should record dimensional fit, airflow, initial pressure and agreed installed-filter test results. Compare the 915 x 610 mm version where the ceiling offers more length, with performance selected for that assembly.
Planning your Cleanroom HEPA Supply Air Terminal 610 x 610 mm Ultra-Thin 600 m³/h specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.