Cleanroom Electric Drop Bolt Lock Monitored Stainless Steel
- Separate monitoring supports more informative interlock feedback.
- Horizontal or vertical installation accommodates different preparations.
- A stainless pin provides a positive mechanical engagement.
Separate closure from positive bolt engagement
This monitored electric drop bolt secures a closed door by extending a stainless steel pin into a matching strike. The mortised body suits a prepared stile or header where projecting locking hardware is undesirable. Its two feedback functions allow the control system to distinguish the door reaching its closed position from the bolt reaching its locking position.
That distinction matters in an airlock. A closed-door signal can exist while the pin is obstructed by an offset strike. The controller should use the agreed combination of feedback before granting the next door permission. Neither contact proves gasket compression, room pressure or the achieved holding strength.
Make the strike alignment repeatable
The closer or primary latch must bring the leaf to its intended position before the pin extends. A drop bolt is not a device for pulling a drifting door into line. Coordinate the bolt travel, strike opening, frame gap and clearance behind the strike using the selected mounting drawing. Provide reinforcement for the complete load path through the strike and frame.
Horizontal and vertical arrangements need an approved orientation. These terms do not establish that an upward-facing bolt is suitable. Keep the pocket accessible for wiring and replacement, and avoid making an enlarged strike hole the remedy for hinge wear or a loose door stop.
Electrical and mechanical selection
| Item | Basis for selection |
|---|---|
| Pin | 12.7 mm stainless steel reference configuration |
| Supply | 12–24 VDC, with tolerance and starting current checked for the offered version |
| Nominal retention | 10,000 N reference class, subject to evidence for the lock and supporting installation |
| Monitoring | Separate door-position and bolt-position connections |
| Mounting | Mortise preparation in a permitted orientation with matched strike |
| Power-loss state | Specify fail-unlocked or fail-locked behaviour for the actual assembly |
The holding reference is a force, not a door-mass allowance or a guarantee of unlocking under side pressure. Size the power circuit for actuation as well as holding duty. Status contacts are signal interfaces with their own ratings, not outputs for directly switching another lock.
Acceptance and routine checks
Test a normal closing cycle, a deliberately misaligned closing position, release under expected door preload and power interruption. Record how the controller handles a closed door with no bolt confirmation. On powered leaves, prevent the operator from driving against a bolt that has not retracted.
Inspect the strike, screws, pin path and cable protection during service. Remove debris and correct door sag before adjusting delay settings. Quote the opening section, mounting orientation, supply, control logic and required feedback. Where authorised mechanical recovery is required, consider the key-override version.