Select normally locked or normally free two-door sequencing with local microcontroller logic and clean relay outputs.
  • Selectable idle logic accommodates different entry arrangements.
  • Busy and alarm outputs distinguish waiting from abnormal door conditions.
  • Optional delay selection helps coordinate successive releases.
Permintaan sebut harga Semak imbas produk

Pengenalan Produk

A dedicated microcontroller supervises two monitored doors and their request inputs. The board uses separate relay contacts for door release, busy indication and alarm signalling, and can be installed in a tamper-switched steel enclosure. Configuration jumpers determine the idle behaviour. The assembled two-door system suits a local airlock where operation should remain independent of Ethernet, while still giving the installer clear connection points for locks and auxiliary indications.

Ciri-ciri Utama

  • Selectable idle logic accommodates different entry arrangements.
  • Busy and alarm outputs distinguish waiting from abnormal door conditions.
  • Optional delay selection helps coordinate successive releases.

Parameter teknikal

Configured Doors2
Controller TypeMicrocontroller board
Nominal Supply12 VDC
Idle SelectionNormally locked or normally free
Door Release ContactSingle-pole changeover
Contact Voltage30 V maximum
Contact Current1 A maximum
Delay Options5 or 10 seconds
Enclosure OptionTamper-switched mild steel
PenyesuaianThe enclosure and connected door devices can suit the local access arrangement.

Applications

  • Personnel airlocks using request-to-exit buttons.
  • Two-door access groups requiring separate busy and fault outputs.

Solutions for Your Application

Waiting for another door resembles a system fault.

Separate busy and alarm contacts provide distinct indications.

Control hardware may be accessible from a corridor.

Select the steel enclosure with a tamper switch.

Pilihan yang boleh didapati

  • White powder-coated enclosure.
  • Normally locked configuration.
  • Five- or ten-second delay selection.