Larger inlet area
The 12-inch collar accommodates branches selected to reduce connection velocity or local entry loss.
This model retains the slim 41 mm H14 pack and 4.75 in module depth but increases the duct collar to 12 in. The larger connection provides more inlet area for a given branch airflow and can ease duct velocity or connection losses where ceiling space allows the wider collar. An integrated diffusion disc spreads incoming air across the filter face behind the protective grille.
The 12-inch collar accommodates branches selected to reduce connection velocity or local entry loss.
Increasing collar diameter does not change the 41 mm pack or low-profile module depth.
The internal diffusion disc redirects collar air across the HEPA pack instead of concentrating it beneath the inlet.
| HEPA Grade | H14 / 99.99% at 0.3 micron |
|---|---|
| Filter Pack Thickness | 41 mm |
| Module Overall Depth | 4.75 in |
| Collar Diameter | 12 in |
| Distribution Device | Integral diffusion disc |
| Module Frame | Extruded aluminum |
| Media Type | Glass fiber mini-pleat |
| Outlet Protection | White epoxy powder-coated steel grille |
| Primary Selection Factor | Larger duct connection in a shallow ceiling terminal |
| カスタマイズ | 意図したアプリケーションと動作環境に基づいて利用できます。 |
Selected for pharmaceutical, hospital and controlled manufacturing ceilings that have very little vertical room but use a 12-inch supply branch. Compare actual branch airflow, available collar diameter and neighboring services before choosing it over the narrower 10-inch model.
Confirm face module size, diffusion-disc control, 12-inch duct takeoff position, grille finish and ceiling-support details.
寸法、設置条件、性能目標、必要な表面仕上げをお送りください。