Votre fournisseur à guichet unique pour les équipements de salle blanche et les essentiels des installations aseptiquesSoutien international aux projets
Open mobile navigationClose mobile navigation
Accueil / Produits / Cleanroom Air Filters / Side-Access HEPA Filter Housing One-Wide
STJH-SIDE-ACCESS-HEPA-HOUSING-1W

Side-Access HEPA Filter Housing One-Wide

A compact single-wide duct housing for one full-size HEPA filter with dual-side service access.
  • One full-size filter wide
  • Either-side access doors
  • Integral 2 in prefilter track
Demander un devis. Browse les produits

Introduction de produit

This galvanized 14-gauge cabinet holds one full-size HEPA filter across the duct width. Doors on either side allow the installer to choose the usable service face, while an integral challenge port supports installed-filter testing and a nominal 2 in track accepts a protective prefilter. The one-wide arrangement fits single-branch systems and avoids the excess face area of a two-cell cabinet.

Key Features

Compact duct footprint

A single filter cell serves smaller critical-air branches without a wide multi-cell enclosure.

Flexible service side

Access doors on both sides let site conditions determine the active maintenance aisle.

Testing and prefiltration provisions

A challenge port and shallow upstream track support HEPA integrity testing and filter-life protection.

Paramètres techniques

Filter CapacityOne full-size HEPA filter wide
Housing Material14-gauge galvanized steel
AccessEither side
Family Pressure CapabilityUp to ±8 in. w.g.
Prefilter Track2 in nominal
Filter SealSwing-bolt or crank compression by configuration
Test ProvisionChallenge aerosol port
Door TypeRemovable dual-side service doors
InstallationDucted final-filter section
CustomisationDisponible en fonction de l'application prévue et de l'environnement d'exploitation.

Applications

For single-duct clean-process, medical and laboratory supply or exhaust systems needing accessible final HEPA filtration without BIBO containment.

Solutions for Your Application

The only clear service aisle is on the opposite side from the factory door arrangement.Use the dual-access design and coordinate instruments, latches and blank doors to keep the selected service side unobstructed.
The HEPA loads rapidly because coarse dust reaches the final stage.Fit the nominal 2 in upstream prefilter and select its grade from the ambient dust profile and available fan static.

Options disponibles

Specify cabinet material, filter face and depth, sealing mechanism, active access side, prefilter, challenge and scan ports, and duct flanges.

Planning a Side-Access HEPA Filter Housing One-Wide specification?

Envoyez-nous vos dimensions, conditions d'installation, objectifs de performance et finition de surface requise.

Parlez à notre équipe
Email nous WhatsApp WeChat

Accueil

Produits

Actualités

À propos

Contact