Defined dissipative duty
The material slows charge dissipation relative to lower-resistance conductive options. Procurement should retain the actual resistance band and measurement method in the floor specification.
This sheet configuration combines a 2 mm full-depth PVC body with dispersed carbon-encapsulated granules. It is selected for a 10^6 to 10^8 ohm resistance band rather than the lower band associated with conductive flooring. The material is bonded and grounded as a complete floor system, with welded seams forming an accessible cleaning surface between workstations and circulation aisles.
The material slows charge dissipation relative to lower-resistance conductive options. Procurement should retain the actual resistance band and measurement method in the floor specification.
Roll coverage reduces the number of individual finish pieces in open electronics areas, helping cleaning teams maintain unobstructed routes under benches and along equipment lines.
The carbon-granule structure runs through the vinyl body, so the selection does not depend on an ordinary decorative sheet receiving a temporary antistatic polish.
| Base Material | Homogeneous PVC |
|---|---|
| Nominal Thickness | 2 mm |
| Electrical Type | Static dissipative |
| Resistance Selection Range | 10^6–10^8 Ω |
| Dissipative Structure | Carbon-encapsulated granules |
| Supply Form | Sheet roll |
| Joint Construction | Heat-welded seams |
| Fixing | Adhesive bonded |
| Earthing Arrangement | Grounded floor system |
| Tùy chỉnh | Có sẵn dựa trên ứng dụng dự định và môi trường hoạt động. |
Suitable for electronics work areas and medical technical rooms calling for a dissipative floor. Combine it with the intended shoes, seating and cleaning procedure, because surface-to-ground resistance alone does not establish the behaviour of a moving operator. Keep spills and insulating residues from accumulating where people stand at sensitive workstations.
Specify dissipative resistance and a named test method so the delivered material matches the room's intended charge-control strategy.
Use a compatible ESD cleaning method and include periodic measurements after cleaning, particularly at frequently occupied bench positions.
Choose the roll colour, seam layout and grounded adhesive package. Detail separate floor zones around expansion joints so electrical connections remain deliberate and maintainable when equipment layouts change.
Gửi cho chúng tôi kích thước của bạn, điều kiện lắp đặt, mục tiêu hiệu suất và bề mặt yêu cầu hoàn thiện.