Standard square integration
The 610 mm face installs in full-module banks without fractional frame adapters.
The 610 × 610 × 292 mm full module is rated for 4000 m3/h at E10 efficiency and an initial pressure drop of 190 Pa. Its compact V-bank construction supports air temperatures up to 120 °C. This balanced full-size model is intended for standard process-air banks that need high throughput without using the expanded-media 5000 m3/h version.
The 610 mm face installs in full-module banks without fractional frame adapters.
The 4000 m3/h rating is paired with a 190 Pa clean drop for conventional high-flow operation.
Temperature-resistant construction extends use beyond normal comfort-ventilation conditions.
| Overall Dimensions | 610 × 610 × 292 mm |
|---|---|
| Efficiency Class | E10 |
| Nominal Airflow | 4000 m3/h |
| Initial Pressure Drop | 190 Pa |
| Maximum Operating Temperature | 120 °C |
| Face Module | Full 610 mm square |
| Filter Depth | 292 mm |
| Pack Geometry | Compact high-area V-bank |
| Intended Service | High-volume clean industrial air |
| Customization | Disponible según la aplicación prevista y el entorno operativo. |
Suitable for high-volume clean industrial supply, warm recirculation air and process systems with standard 610 mm filter banks. It provides a practical E10 module where elevated temperature capability is needed but the maximum 5000 m3/h throughput is unnecessary.
Specify header configuration, gasket material, airflow direction and continuous operating temperature for the process bank.
Envíenos sus dimensiones, condiciones de instalación, objetivos de rendimiento y acabado superficial requerido.