Cleaning-compatible seal choice
EPDM offers a practical gasket interface for rooms where terminal surfaces are regularly wiped with compatible disinfectants.
The 70 mm panel provides H14 filtration in a balanced-depth mini-pleat format. Its continuous EPDM gasket is selected where the seal is exposed to routine cleaning agents and needs repeatable elastic recovery after clamping. An anodized aluminum perimeter protects the microglass pack and fits conventional gasket-seat terminals without the gel channel required by fluid-seal systems.
EPDM offers a practical gasket interface for rooms where terminal surfaces are regularly wiped with compatible disinfectants.
H14 performance addresses more demanding particle-control specifications than the shallow H13 model in this gasket family.
The flat gasket seats against a smooth housing land and does not require a gel-filled receiver channel.
| Filter Medium | Microglass mini-pleat |
|---|---|
| Filter Classification | H14 |
| Media Pack Depth | 70 mm |
| Perimeter Frame | Anodized aluminum |
| Gasket Material | Continuous EPDM |
| Seal Engagement | Uniform face compression |
| Separator System | Hot-melt pleat spacing |
| Typical Installation | Gasket-seat cleanroom terminal |
| Maintenance Focus | Inspect gasket recovery and sealing land at changeout |
| Customization | Доступно в зависимости от предполагаемого применения и операционной среды. |
Suitable for pharmaceutical, healthcare and controlled-process ceilings where H14 efficiency and a resilient dry gasket are preferred. It is especially relevant when sanitation chemicals make gasket material selection important, provided the chosen EPDM formulation is compatible with the site's cleaning agents.
Select final face size, gasket location, upstream or downstream grille, and an EPDM compound compatible with the cleaning program.
Отправьте нам ваши габариты, условия монтажа, целевые показатели производительности и требуемую отделку поверхности.