Stainless Steel Welded Air Duct 304 Mill-Finish
- Continuous welded seams replace folded longitudinal joints.
- Unbrushed faces provide a straightforward utility finish.
Use welded 304 duct where a utility stainless surface is appropriate
This duct construction uses 304 stainless sheet with continuous TIG fabrication seams and a specified post-weld surface treatment. It is intended for air routes where a stainless shell and welded joints are useful, while a decorative brushed exterior is unnecessary. Selection still depends on the air chemistry, moisture and cleaning exposure; a 304 designation does not make every exhaust service suitable.
Define the fabricated section rather than ordering by gauge alone
| Reference | Order requirement |
|---|---|
| 304 stainless; mill finish | Material certificate and the actual mill surface required on the air side and outside. |
| 20–10 gauge reference fabrication range | Specify decimal thickness and tolerance for the duct dimensions, pressure and reinforcement design. |
| 1524 mm nominal section reference | State finished face-to-face length and how end allowances affect the installed run. |
| 12.7 mm field-weld flange reference | Define its profile and projection on a drawing; this number alone does not identify a bolt pattern or flange thickness. |
Round and rectangular ducts have different structural behaviour. A broad flat side may need stiffeners even when the sheet is described as heavy gauge. Both positive pressure and suction conditions should be included in the construction design.
Separate weld cleaning, passivation and leakage control
TIG identifies a welding process, not proof of a sound or smooth seam. Define weld continuity, accessible internal profile and inspection requirements. Post-weld treatment must address contamination and heat tint as appropriate; chemical passivation is not a universal substitute for removing scale or correcting weld defects.
Factory-welded longitudinal seams also do not seal every site joint. Coordinate field welds, bolted equipment connections and access-door seals, then test the agreed installed boundary. Longer sections reduce joint count but increase handling and access requirements.
Installation and maintenance
Protect the stainless surface from carbon-steel grinding debris and contaminated tools. Support sections without forcing alignment through equipment flanges. Specify external insulation and vapour sealing separately where cold-air service may cause condensation.
Provide access for the expected deposits and use cleaning agents compatible with 304 and all joint materials. Investigate staining or pitting rather than assuming stainless needs no inspection.
Quotation and acceptance
Supply the route, section geometry, pressure duty and air composition. Quote material, thickness, reinforcement, finished lengths, joints, weld treatment and inspection/test scope explicitly. Accept against the drawing, material records, agreed weld and cleanliness criteria and specified leakage test; no sanitary or pressure rating follows from mill finish alone.