Single MgO Rock Wool Cleanroom Panel 50 mm Machine-Made Wall
- One reinforced side avoids a second board layer.
- Continuous formed edges suit regular partition runs.
One board layer creates an oriented wall panel
The 50 mm single-MgO machine-made panel places one mineral board beneath a selected steel face, with rock wool behind it and a second metal skin on the opposite side. This asymmetric construction is useful when one face needs the specified backing and a double-board section is unnecessary for the chosen design.
Keep the orientation visible in the schedule
The backed face must be identified on the drawing and on the delivered module. Two finished metal surfaces can look alike after installation, while the internal build-up differs. The correct side is determined by the intended use and performance evidence, rather than simply whichever face is easier to install toward the room.
A single board reduces the board content compared with an otherwise equivalent double-board build-up, but it does not make both faces behave identically under load. State the loading and exposure direction in any structural or fire-performance requirement. Reversing a tested asymmetric construction may change the applicability of its evidence.
Dimensions, joints and services
The reference format is 50 mm overall thickness with 950 or 1150 mm effective cover width, 0.3–0.6 mm steel faces and an approximately 5 mm MgO backing. The rock-wool reference density range is 100–140 kg/m³. Board and metal thicknesses occupy part of the overall depth, so insulation calculations need the actual remaining core thickness.
Tongue-and-groove edges locate the continuous-line panels. Their interlock does not remove the need for the specified air and cleaning seals. Service boxes and cut openings need closure around all exposed layers. A backed skin is not automatically an anchorage for a heavy bracket; use local reinforcement or independent support appropriate to the load.
Procurement and upkeep
Provide elevations, orientation marks, service locations, supported height and cleaning conditions. Identify panel build-up, coating, joint components, tracks and seals in the quotation. Require the actual board material and moisture-compatibility information rather than treating all MgO formulations as equivalent.
Acceptance should check orientation, dimensions, face condition, bonding and sealed interfaces. Keep dry during storage and protect cut edges during assembly. In service, investigate impact damage on either face and any moisture-related staining or delamination. A replacement should match the intended orientation and construction, not merely the nominal 50 mm depth.
Planning your Single MgO Rock Wool Cleanroom Panel 50 mm Machine-Made Wall specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.