Home / Products / Air Ducts & Air Distribution / Single-Duct VAV Reheat Terminal Unit DN200 Electric
zhengfeng-SINGLE-DUCT-VAV-REHEAT-TERMINAL-DN200-ELECTRIC

Single-Duct VAV Reheat Terminal Unit DN200 Electric

coordinate heater output, minimum heating airflow, thermal protection, power service and accessible controls.
  • Electric heat avoids a local hydronic branch.
  • Separate heater enclosure keeps power components accessible.
Request a Quote Browse Products

Electric reheat coordinated with variable airflow

The DN200 single-duct VAV terminal adds resistance heating downstream of its airflow-control section. It provides local temperature trim where a hot-water branch is impractical. The heater requires a selected electrical supply and protection package in addition to the low-voltage airflow controller.

Heating airflow is a design limit

For a given heater output, air temperature rise increases as airflow falls. The heating sequence must therefore establish the minimum permitted flow for the selected heater and limit discharge temperature as required. A cooling minimum is not automatically a safe or suitable heating minimum.

An airflow interlock and automatic and manual-reset thermal cutouts form the specified protection arrangement. Their devices and wiring must match the supplied heater. A normal airflow-control reading does not replace the heater interlock, and a thermal cutout is protection rather than a routine temperature controller. Repeated trips require investigation before operation resumes.

Compare staged and modulated heat

ChoicePractical effect
Staged outputProvides discrete heat increments; stage size affects temperature swings at low load.
SCR modulationVaries average electrical output more finely, with compatible control signals and heat-rejection requirements.
Discharge sensorSupports the selected supply-temperature control or limit sequence.
Electrical enclosure positionMust preserve working and removal access after duct and ceiling installation.

The reference element construction is low-watt-density nickel-chromium within a galvanized terminal assembly. Element material alone does not define permissible kilowatts, air velocity or approvals. Specify voltage, phase, available power, disconnecting arrangement and the exact heater configuration.

Install for even flow and accessible service

Provide the inlet and heater-clearance arrangement required by the selected unit. A distorted approach profile or obstructed heater passage can create local hot spots even when total airflow appears adequate. Pressure-independent airflow control remains limited by the available pressure and calibrated flow range.

Quote the terminal, heating output, controls, sensors, protection and power interfaces as a complete package. Commission the airflow limits, heating steps or modulation, discharge temperature and specified loss-of-airflow response. Coordinate minimum ventilation and room-pressure requirements with the control sequence. Maintenance requires electrical isolation, inspection of deposits and connections, and investigation of any failed protection or abnormal heating.

Planning your Single-Duct VAV Reheat Terminal Unit DN200 Electric specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.