Single-Duct VAV Reheat Terminal Unit DN150 Hot-Water
- Hydronic reheat uses an available hot-water circuit.
- Multipoint sensing supports pressure-independent airflow control.
Minimum ventilation with local hot-water temperature trim
The DN150 single-duct VAV terminal combines an airflow-sensing inlet, motorized damper and downstream hot-water reheat coil. It can reduce cooling airflow as a small zone load falls, then add heat when the required minimum ventilation would otherwise overcool the room. The upstream air-handling system still determines the available supply temperature and moisture condition.
Choose the minimum flow before selecting the coil
Minimum airflow must satisfy the ventilation, process and room-pressure requirements as well as the reliable measuring range of the terminal. A comfort-room turndown sequence should not be applied unchanged to a controlled room that needs a fixed air quantity or coordinated extract flow.
Pressure-independent control uses measured airflow to reposition the damper as duct pressure changes. It works within the selected flow and pressure range; an open damper cannot deliver the target if upstream pressure is insufficient. The multipoint probe requires a suitable inlet approach and a controller calibrated for the actual assembly.
Hydronic selection and interfaces
| Item | Selection basis |
|---|---|
| DN150 inlet | Nominal format; confirm actual connection dimensions and required straight approach. |
| Hot-water coil | Airflow, entering air, water temperatures, flow and pressure losses. |
| 1/2 in connection reference | Confirm tube outside diameter or nominal pipe size, joint type and handing. |
| Galvanized casing and rectangular outlet | Match the slip-and-drive or selected connection and maintain access to the coil. |
Pipe diameter does not establish heating capacity. Select the control valve and hydraulic balance with the coil, and support pipework independently so it does not load the headers. Provide access for isolation, venting, leakage inspection and eventual coil service.
Define and prove the operating sequence
Specify cooling maximum, ventilation minimum, heating airflow, water-valve control and any discharge-temperature limit. Reheating raises dry-bulb temperature and can lower relative humidity, but it does not remove water vapor. Required dehumidification belongs in the complete conditioning design.
The quotation should identify controller, actuator, sensors, valve package, coil, lining and electrical interfaces. At handover, measure flow at the selected limits, check heating conditions and demonstrate coordination with extract and room pressure. Inspect sensing tubes, probe cleanliness, damper travel and water connections during maintenance.
Planning your Single-Duct VAV Reheat Terminal Unit DN150 Hot-Water specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.