Powder-Coated Steel Cleanroom Door Rock-Wool Core
- Window-free construction preserves visual privacy.
- A continuous coated face avoids glazing-to-leaf junctions.
- Mineral infill provides a distinct alternative to paper or metal-cell cores.
Opaque mineral-core access to clean utility rooms
This single swing door has rock-wool infill between powder-coated steel faces and no observation window. It suits utility rooms where visual separation and a continuous opaque surface are useful. The lack of a glazing junction simplifies the face detail, but the perimeter, hinges, lock and bottom edge remain cleaning and maintenance points.
An opaque door limits the user's view of the opposite approach. In a busy route, assess opening direction and traffic management; where visibility is essential, select an appropriately glazed doorset. Privacy should not be achieved at the expense of an unsuitable approach arrangement.
Reference construction and what it does not establish
| Parameter | Listed reference |
|---|---|
| Operation | Manual hinged single opaque leaf. |
| Leaf thickness | 50–62 mm; selected thickness coordinated with the frame and hardware. |
| Steel faces | 0.8–1.0 mm with powder-coated finish. |
| Infill | Rock wool; listed core-density range 100–135 kg/m³, to be confirmed for the selected build. |
| Frame | Powder-coated metal with single-flush or semi-flush integration options. |
| Hardware | Compatible closer and lever options; sealing and latching schedule defined per opening. |
The mineral infill is enclosed within the leaf. Its density is a construction input, not a certified fire duration, sound rating or allowable impact load. A rated boundary requires a tested or approved assembly with the permitted frame, hardware, seals, wall and size. Adding a closer to a nonrated leaf does not create that assembly.
Core and facing changes can affect the leaf mass. Select hinges, closer reinforcement and supporting jambs from the complete door schedule. A thicker steel skin also does not correct an inadequate partition anchorage or damaged edge bond.
Installation and routine service
Coordinate flushness with the actual wall finish and the side that needs easiest wiping. Anchor the frame squarely, maintain the specified clearances and close the frame-to-wall junction with a compatible detail. Decide the bottom clearance and sealing arrangement alongside the pressure strategy; this product description does not establish a quantified air-leakage value.
Keep leaf edges intact so mineral fibers remain enclosed. Investigate a swollen or distorted face, loose edge closure or water ingress rather than covering damage with fresh coating. Clean the finish according to the approved chemical procedure and repair chips before corrosion spreads. Check hinges and latching after any adjustment to room pressure or the closer.
Price scope and acceptance
Include opening size, wall construction, selected core/skin build, finish, handing, lock, closer, seals and installation in the request for quotation. Fire or acoustic documentation, if required, must be specified as part of the procurement scope. Handover should verify frame alignment, clear passage, complete edge closure, finish condition and repeatable operation under the normal room pressure. Record the supplied assembly details so future hardware changes can be assessed against any required rating.
Planning your Powder-Coated Steel Cleanroom Door Rock-Wool Core specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.