PIR Pre-Insulated Air Duct 20 mm Standard
- Intermediate wall depth balances insulation and duct bulk.
- Closed-cell core reduces moisture absorption within the panel.
Combine an indoor air passage and insulation in one system
The 20 mm PIR duct uses aluminum-faced rigid sandwich panels to form the air passage and thermal layer together. It can simplify an indoor supply or return layout where separate metal duct and external wrap would occupy more space or require additional site operations. The panel, connectors, sealants and supports must be selected as a coordinated duct construction.
Match the complete system to supply and return pressure
Supply pressure tends to expand the section; return suction can pull faces inward. The same panel thickness does not establish identical capability in both directions. Select permissible face widths, reinforcement and joint spacing from data for the actual panel-and-connector combination. Mixing an available flange with an unrelated board can invalidate the basis for structural and leakage performance.
| Catalog reference | Project definition |
|---|---|
| 20 mm PIR wall | Declared conductivity and thermal calculation at the scheduled service conditions. |
| Primed aluminum facings | Inner and outer facing specifications, adhesion and permitted cleaning exposure. |
| 1200 mm wide stock panels, 2000–4000 mm long | Cut geometry and finished duct dimensions rather than assuming stock size equals section size. |
A uniform panel thickness helps control the field insulation layer, but flanges, access doors and support points can interrupt it. Check those details for heat transfer and vapour continuity. Closed-cell foam does not make open cut edges or failed joints waterproof, and core density is not a verified duct stiffness or fire rating.
Fabrication and service access
Seal the internal joints and exposed edges to preserve a continuous air-side lining. Coordinate bends and reducers so joints remain accessible and the clear passage is maintained. Provide compatible equipment adapters; do not hang a heavy damper or terminal from an unsupported foam wall.
Protect facings during handling and keep construction debris out. Provide access for the approved cleaning tools and inspect joints, support crushing and delamination during service. Avoid wet or abrasive treatment unless the supplied system specifically supports it.
Quotation and acceptance basis
Submit the route, section dimensions, pressure envelope, thermal conditions and cleaning requirements. Include panels, profiles, adhesives, edge treatment, reinforcement, supports and leakage testing in the quote. Require applicable duct-system and reaction-to-fire evidence with the accessories identified. A general HVAC application does not establish suitability for smoke extract, grease exhaust or a cleanroom classification.