Phenolic Pre-Insulated Air Duct 20 mm
- Double aluminum faces enclose the rigid foam.
- A 20 mm wall suits ordinary indoor air-conditioning routes.
Form an insulated indoor duct from faced phenolic panels
The 20 mm phenolic option uses a rigid foam core with aluminum facings on both sides. Fitted panel joints form a rectangular air passage while the core provides insulation. It is an indoor HVAC construction choice whose suitability depends on the complete fabricated system, including edge sealing, connectors and supports.
The facing must remain continuous at more than the panel surface
Foil encloses the foam on an intact sheet, but cutting and joining expose edges. Specify the internal seam and edge treatment so the air stream meets the intended lining throughout corners, takeoffs and equipment interfaces. A groove-and-tongue joint helps locate parts; it does not by itself provide an air seal, vapour seal or structural rating.
| Reference | Specification task |
|---|---|
| 20 mm phenolic core; 1200 × 2400 mm stock panel | Define the finished clear passage and section lengths after cutting and jointing. |
| Aluminum facing, 0.08 mm per side reference | Verify the actual facing, coating and bond specification. |
| Fitted panel construction | Use compatible profiles, adhesive, sealant and reinforcement with documented duct performance. |
Use declared thermal conductivity and service limits for the supplied system; a foam value alone does not establish the temperature capability of adhesives, facings and seals. Pressure resistance and leakage depend on section dimensions and joints. Reaction-to-fire classification of a board is also different from fire resistance of a complete duct route.
Plan a cleaning method appropriate to a foil lining
A hospital-support application does not establish antimicrobial performance, sterility or tolerance of every disinfectant. Determine the expected deposits and cleaning method before selection. Thin foil can be damaged by sharp tools or aggressive cleaning, exposing the core and weakening the barrier. Provide inspection doors and an approved repair method for damaged lining.
Support sections on suitable load-distributing details and connect heavy equipment independently. Protect the duct from moisture and construction debris, and inspect cut edges and seams before they become inaccessible.
Supply scope and acceptance
Quote panels, profiles, edge treatment, support/reinforcement, access provisions and tests. Provide the operating pressure, thermal conditions and hygiene requirements. Acceptance should verify material identity, intact lining, dimensions, installed joint sealing and the agreed pressure/leakage criteria, supported by system-specific documentation rather than generic phenolic claims.