Perforated Steel Raised Access Floor 65% Open-Area Grate
- 65% ventilation opening area
- 600 x 600 x 35 mm module
- Epoxy-coated all-steel grate
An open steel grate for localized airflow
This nominal 600 × 600 × 35 mm module uses an all-steel grate with an epoxy-coated surface. The 65% opening designation describes the selected geometric arrangement, which should be verified on the supplied drawing. Compared with a round-hole sheet, the grate exposes wider openings between load-bearing members.
The module is useful where a large air path is needed within a limited number of floor positions. Delivered airflow still depends on plenum pressure, bar geometry and obstructions below or above it. Use a pressure-flow curve for the final panel rather than calculating airflow from open area alone.
Check contact with the remaining steel
Small wheels, narrow feet and footwear must be assessed against the actual opening dimensions. A foot partly spanning a gap imposes a different load from a broad plate covering several bars. A concentrated-load claim is incomplete without the test contact area, support and deformation criteria; obtain a report for the selected assembly.
Concentrated-load evidence also does not establish repeated rolling capacity. Keep incompatible equipment contacts on solid supports or a separately evaluated transport route. The bearing-member direction and its end seating are structural details that must be retained.
Interfaces and access
Check the 35 mm panel depth, seat geometry and finished level against neighboring modules. Provide secure retention where the floor design requires it. Do not cut bars or enlarge apertures on site to clear a cable route. A modified grate needs a reviewed structural and edge detail.
Keep lifting positions accessible and provide a cleanable route into the void. The open face does not prevent small objects or liquid entering below, so its position must suit the room process. Coating damage at bar edges or supports should be repaired by the approved method.
Purchase and acceptance
Specify dimensions, opening geometry, load cases, coating, supports and any regulator as separate items. Include transitions and airflow commissioning in the quotation where required. Acceptance should verify fit, seating, coating condition, structural evidence and actual flow. Record locations so later substitution with solid panels does not change the ventilation layout unnoticed.