Perforated Face Air Diffuser 593 mm with DN125 Connection
- Perforated front conceals the directional blade assembly.
- Small connection suits modest supply branches.
Concealed swirl behind a modular perforated face
This diffuser places a fixed-blade swirl element behind a 593 x 593 mm perforated panel. The DN125 connection suits a small supply branch while the visible panel follows the surrounding ceiling appearance. The internal blades turn the supply so it entrains room air and mixes with it; the perforated sheet conceals the mechanism. Neither component filters the air.
Two independent dimensions
| Selection item | Catalog reference |
|---|---|
| Face | 593 x 593 mm perforated galvanized steel. |
| Connection | DN125 nominal; actual spigot and joint dimensions by selected drawing. |
| Finish | RAL 9010 white face; RAL 9005 black internal swirl element. |
| Discharge | Horizontal swirl from fixed blades. |
| Connection options | Vertical collar or horizontal-entry plenum, with optional internal lining. |
The 593 mm panel is a ceiling interface, not an indication of a large active outlet. Size the internal element and connection from the required airflow, available pressure, sound limit and throw. A small branch can become noisy if forced to carry a duty selected merely from the panel area. Enlarging the face alone does not solve that restriction.
Use the plenum choice to solve the ceiling route
A vertical collar needs space directly above the terminal. A horizontal box brings the branch in from the side but adds a separate envelope, suspension and access requirement. Keep the diffuser aligned and support the duct so it cannot pull the thin face out of shape. Coordinate the ceiling bearing and panel removal method before choosing exposed or concealed grid details.
Internal lining may be useful for acoustics, but its surface protection, cleaning method and suitability for the intended controlled area must be part of the specification. Acoustic lining should not be treated as filtration or as external condensation insulation. For humid voids and cold supply, detail the insulation and vapour seal at the collar and joints.
Cleaning, quotation and release checks
Deposits can collect on the perforated plate and hidden blades. Provide access to both without bending the blade geometry or plugging the perforations with coating. Refit the face securely after cleaning and use the specified airflow measurement method rather than multiplying a random face velocity by the gross panel area.
Price the panel, swirl assembly, chosen box or collar, lining, balancing device and fixing hardware explicitly. Acceptance should verify ceiling fit, access, measured volume, sound and room distribution at the intended supply temperature. A support-room mixing outlet does not substitute for a HEPA terminal or an open-process protection device.
Planning your Perforated Face Air Diffuser 593 mm with DN125 Connection specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.