Opposed Blade Volume Control Damper 300 x 300 mm Steel
- Opposed motion meters air through multiple openings.
- Slotted operator accepts a standard flat screwdriver.
Adjust volume without resetting the directional blades
The 300 × 300 mm steel opposed-blade damper provides a separate manual balancing element behind a grille or at a suitable duct interface. Linked blades rotate in alternating directions when the slotted operator is turned. This changes the total passage while allowing the visible directional louvers to remain at their selected angles.
Blade angle is not percentage airflow
The relationship between operator position and flow depends on pressure and the surrounding system. Half travel does not establish half the design volume. Balance with an appropriate airflow measurement, then secure the setting using the supplied mechanism and record the final position.
Opposed motion distributes throttling among several passages, but it does not eliminate pressure loss or air-generated sound. A nearly closed damper behind the grille can become the dominant noise source. If substantial pressure must be dissipated, review the branch arrangement and upstream balancing provision.
Make the operator reachable
| Feature | Coordination requirement |
|---|---|
| 300 × 300 mm nominal frame | Confirm actual insertion size, depth and grille attachment. |
| Coated-steel construction | Specify coating compatibility with the air and cleaning exposure. |
| Linked opposed blades | Allow the full blade sweep without contact with screws or adjacent fittings. |
| Slotted operator | Provide a clear screwdriver route through the selected face. |
A slotted operator suited to one grille may be obscured by another blade pattern. Confirm the complete face-and-damper combination before manufacture. Distorted frames or screws projecting into the movement path can make the adjustment stiff and prevent all blades reaching the intended position.
Service and scope of supply
Inspect the linkage and blade edges for deposits, damage and free movement. Clean by the approved method without coating pivots indiscriminately. After face removal or other work that may disturb the operator, restore the recorded setting and check flow.
Specify design airflow, pressure drop, sound, exact grille interface, access and setting retention in the quotation. Acceptance should demonstrate full travel, secure mounting and measured terminal flow. This unpowered balancing damper does not automatically maintain airflow and should not be treated as a rated fire, smoke or gas-tight isolation device.