Networked Multi-Door Cleanroom Interlock System Decentralized 16-Door Network
- Local modules keep door connections near each opening.
- Plug-in modules support a planned expansion layout.
- Configuration does not require a programming computer.
Put door connections close to the opening
The decentralized system places a control module near each associated door and links modules through the specified plug-in connections. Locks, indicators, sounders and return signals are connected locally. This can simplify field wiring in a modular cleanroom suite compared with taking every device cable back to one large cabinet.
The sixteen-door designation describes the maximum intended network configuration, not a requirement that every door belongs to one exclusion group. Map each door to the rooms it connects, then define which other doors it must inhibit. Two independent vestibules should not unnecessarily stop one another, while a shared door must participate in every relevant relationship.
Expansion requires both logic and power capacity
Adding a module changes the connected load, cable path and possible failure effects. Check the supported module combination and topology before extending a running suite. A plug that physically fits does not establish compatible pin assignments or firmware. Treat proprietary control connections as such, even when their connector resembles a familiar data connector.
| Configuration point | Planning reference |
|---|---|
| Network size | Up to sixteen doors within the selected system configuration |
| Control location | Distributed modules with local parameter settings |
| Lock output | 24 VDC, 1 A reference per specified locking interface |
| Sounder output | 24 VDC, 20 mA reference |
| Traffic-light output | 24 VDC, 50 mA reference |
| Feedback | Door return-signal interface, with its physical meaning documented |
These are interface references, not a combined power-supply rating. Sixteen nominal lock outputs do not prove that a supply can deliver sixteen amperes at the farthest module. Sum the actual connected loads, check cable voltage drop and account for permitted operating combinations. A higher-power horn or lamp may require a separately powered interface rather than connection to a low-current indication output.
Identify what survives a module or link fault
Distributed wiring does not automatically mean each door continues independently after a communications fault. Define which doors are inhibited, which indications appear and how a valid closed or locked state is re-established when a module loses power or a connection is removed. Emergency operation must follow the approved release arrangement, including any backed-up supplies.
Local parameter setting avoids a programming computer for routine configuration, but the installed settings still need a record. Label modules by door and room, document relationships and preserve a replacement procedure. A spare module with default settings can create different behaviour even when all plugs reconnect correctly.
Acceptance for a complete suite
Test permitted and conflicting requests across the relevant groups, especially shared doors. Include a module power loss, broken interconnection, an open door during restart and emergency release. Check the farthest device under the expected electrical load. These tests verify the installed arrangement rather than the module count alone.
Provide the room plan, door relationship schedule, module locations, cable lengths and connected lock and indicator loads for quotation. Compare an Ethernet master and remote-I/O system when the project needs centrally engineered sequences or wider facility interfaces.