Home / Products / Air Ducts & Air Distribution / Motorized Volume Control Damper 400 x 345 mm Opposed-Blade 10 Nm
zhengfeng-MOTORIZED-VOLUME-CONTROL-DAMPER-400X345-10NM

Motorized Volume Control Damper 400 x 345 mm Opposed-Blade 10 Nm

A compact motorized blade bank provides commanded positions, with airflow regulation defined by the external control design.
  • Opposed blade movement suits progressive volume adjustment.
  • Position feedback is available for control-system indication.
Request a Quote Browse Products

Position a compact opposed-blade damper automatically

This 400 × 345 mm assembly combines opposed aerofoil blades with an external linkage and a nominal 10 Nm modulating drive. Adjacent blades rotate in opposite directions as the actuator changes opening. The arrangement provides adjustable resistance in a branch; a separate airflow measurement and controller are needed when the objective is to regulate measured volume.

Torque selection must describe the actual damper duty

A motor rated at 10 Nm must be matched to the actual operating load of the damper. Required torque depends on differential pressure, blade and bearing construction, seal friction, linkage geometry and installation alignment. Obtain the operating and breakaway requirements for the supplied assembly and select the drive with the appropriate allowance. Extra torque must not be used to force a distorted frame or jammed blade.

Reference configurationInterface to confirm
400 × 345 mm galvanized frameOpening versus overall dimensions, connection and pressure duty.
10 Nm actuator selectionModel, usable torque, shaft fit, travel and mounting bracket.
24 V AC/DC; 2–10 V command and feedbackActual wiring, supply load, direction and signal scaling for the selected drive.

Analogue feedback normally reports actuator position. It does not prove branch airflow, tight closure or that every blade followed the shaft if a link has slipped. Define any independent end switch and the required response to signal loss separately from power loss. A standard modulating drive does not inherently return to a safe position.

Install for unobstructed movement and service

Keep the frame square, leave linkage clearance and align the shaft clamp without side loading. Provide space beyond insulation to reach the actuator and manual release. Check blade travel mechanically before commissioning the powered drive.

During service, inspect loose clamps, worn links and the relationship between indicated and actual position. Review control tuning if the actuator repeatedly reverses; excessive cycling may originate in the external control loop rather than the motor.

Quotation and acceptance

Provide airflow and pressure conditions, desired control function, signal requirements and environmental exposure. Quote the damper, drive, bracket, switches and controls scope explicitly. Demonstrate full and intermediate positions under the agreed operating load, verify feedback scaling and test specified failure behaviour. Flow regulation or leakage performance requires its own measurement and acceptance criteria.

Planning your Motorized Volume Control Damper 400 x 345 mm Opposed-Blade 10 Nm specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.