Home / Products / Air Ducts & Air Distribution / Motorized Shut-Off Damper DN250 Class 4 230 V 5 Nm
zhengfeng-MOTORIZED-SHUT-OFF-DAMPER-DN250-230V-5NM

Motorized Shut-Off Damper DN250 Class 4 230 V 5 Nm

A round EPDM-sealed shutoff blade with a mains-powered actuator selected for the branch control and pressure conditions.
  • The supply arrangement suits installations with mains actuator wiring.
  • The circular casing connects directly to matching round ductwork.
Request a Quote Browse Products

Mains-powered isolation on a DN250 branch

The DN250 galvanized round body contains an EPDM-sealed shutoff disc driven by a nominal 230 V AC, 5 Nm actuator. It provides an on-off branch function where the control design includes a mains-powered actuator. A circular casing can connect to matching round ductwork without introducing a rectangular transition.

Supply voltage and command signal are separate choices

A 230 V supply label does not define whether the selected actuator uses a switched-live command, a multiwire reversing circuit or another approved scheme. Use the actual actuator diagram and interface ratings. The building controller may require an isolating relay; power, control and position-feedback terminals must be coordinated as specified.

ItemCatalog selection
Duct sizeDN250 nominal.
Body/sealGalvanized steel with EPDM-gasketed circular blade.
Actuator5 Nm nominal output and 230 V AC supply.
ControlOn-off, with exact wiring and failure behaviour defined by the selected drive.
AccessoriesBracket, position indication and circular connectors.

The Class 4 name refers to the requested closed-blade leakage classification. Require supporting data for this assembly and pressure; casing and installed-joint leakage need separate consideration. The 5 Nm output must be checked against the torque requirements of this exact damper and duty.

Installation and operating limits

Maintain shaft alignment and the actuator's anti-rotation support. Leave space around the electrical enclosure and coupling, route cables with the required protection and provide the specified isolation means for service. Do not bury the drive in duct insulation. Check that connector screws cannot strike the blade.

Opening and closing under differential pressure can demand different torque. Include seal friction, temperature, deposits and the required operating cycle in the selection. On-off actuation is not continuous pressure or airflow regulation, and it does not imply automatic closure when supply power is lost.

Quotation and verification

Specify the actuator model, duty pressure, leakage requirement, supply/control interface, fail position, enclosure suitability and accessory scope. Inspect the EPDM edge and blade seat during service; gasket damage cannot be remedied reliably by forcing the coupling further.

Acceptance should include the wiring and protective arrangements, correct rotation, full stroke, feedback against actual blade position and the specified failure test. Document leakage for the selected pressure and standard edition. The assembly is a ventilation shutoff device; a fire/smoke or hazardous-process isolation duty needs its own applicable qualification.